This product is designed to display the position codes and Chinese character information of detectors that have triggered alarms, while simultaneously emitting audible and visual alarm signals. It connects to the fire alarm controller via a communication bus to process and display data transmitted from the controller. When a single alarm controller monitors multiple floors or fire compartments, a fire display panel can be installed on each floor or in each fire compartment to show alarm information.
Full Chinese LCD display
Synchronized audible and visual alarm signals with the alarm controller
Four operational function keys: mute, up, down, and query
Loop bus wiring mode
Working voltage:
Power supply voltage: DC24V, allowable range: DC20V~DC28V
Bus voltage: 24V, allowable range: 15V~28V
Working current:
Bus monitoring current ≤3mA, bus starting current ≤3mA
Power monitoring current ≤20mA, power starting current ≤100mA
Alarm records display capacity: 1024 items
Communication distance: <1500m
Maximum number of fire display panels per loop: 32
Operating environment: Temperature 0℃~40℃, relative humidity ≤95%RH (at 40±2℃), non-condensing
Color: ABS, ivory white
Weight: Approximately 300g